Ultimate Guide to Digital Output Module Selection: Mastering the Core Logic and Practical Skills Load Switching​ Jan 10, 2026

Ultimate Guide to Digital Output Module Selection: Mastering the Core Logic and Practical Skills for Loaditching

In industrial automation systems, the digital output (DO) module serves as a "bridge" connecting the controller to the field actuators. Its load switching capability directly the reliability, stability, and lifespan of the system. Whether it's controlling solenoid valves, driving motors, or triggering indicator lights, choosing the right DO module can avoid such as equipment burning and frequent failures. Conversely, it can lead to production interruptions and even major safety hazards.

This article, based on technical documents and practical cases from brands such as Beckhoff, Siemens, and Analog Devices, breaks down the selection logic of DO modules in load switching scenarios. From load characteristic analysis to protection design, helps you solve the selection problem in one stop.


Step 1 of Selection: Understand What Your "Load" Is?

The load is the core basis for DO selection. The electrical characteristics and switching requirements of different loads vary greatly. Blind selection will inevitably lead to failed matching. It is recommended to define the load accurately from 4 dimensions
1. Load Type: Inductive / Resistive / Capacitive, three types of loads are completely different
Resistive Load: Current is linearly related voltage, no storage effect, such as indicator lights, heaters. There is no voltage spike during switching, and the impact on the module is minimal, with the lowest selection.
Inductive Load: Motors, relay coils, solenoid valves, etc. belong to this category. Switching will produce a reverse electromotive force (voltage spikes can reach 5-10 times the power supply voltage), which is the main "killer" of the module. For example, when switching a 24V motor, a module without protection may encounter a voltage impact of over 200V, directly burning out the output channel.

Capacitive Load: Capacitors the input side of frequency converters, etc., will produce a huge surge current in an instant when powered on, which can easily trigger the module's overcurrent protection or the switching elements.


2. Key Electrical Parameters: Voltage and current are hard indicators
Rated Voltage: Define the working voltage of the load (such as24V DC, 230V AC), and select the module of the corresponding voltage level. For example, to control a 24V DC solen valve, you need to select a DC output module, and to drive a 230V AC motor, you need an AC output module. Mixed use is not allowed

Rated Current and Surge Current: The current when the load works normally is the rated current, and the peak current at startup is the surge current (the surge current inductive/capacitive loads can be 3-10 times the rated value). The single-channel output current of the module must be greater than the load rated current and the peak current needs to cover the surge demand. For example, the Siemens QY10 module has a maximum load current of 8A per channel, suitable driving high-power motors; while the S7-1200 series transistor module has a single-channel current of 0.5A, only suitable for low- solenoid valves.


3. Switching frequency: High-frequency switching requires "High-speed module"
The upper limit of the switching frequency varies between different modules, exceeding the frequency limit can cause the module to overheat and the contacts to burn:
Low frequency scenarios (≤1Hz): Such as intermittently workingers, manually controlled valves, relay output modules fully meet the requirements.
High frequency scenarios (≥1kHz): Such as solenoid valves for high-speed sorting machines servo motor brakes, it is necessary to choose a transistor or solid-state relay (SSR) output module, which has a switching frequency of more than 100 and does not have mechanical wear problems.


4. Installation environment: Strengthen the protection level for harsh environments
The temperature, humidity, and electromagnetic interference of the site directly affect the module's lifespan:
Normal environment (–10°C~ 50°C, no strong interference): Ordinary industrial-grade modules do (IP20 protection).
Extreme environment (–25°C~ 60°C, high humidity, strong electromagnetic interference): It is necessary choose a module with wide temperature design and enhanced EMC protection, such as the Beckhoff KL3104 module, which has a working temperature range of –25° to  60°C and is designed to resist electromagnetic interference, suitable for outdoor or heavy industrial scenarios.

II. Core decision: How to choose among the three of output modules? (Relay / Transistor / SSR)
DO modules are divided into three categories according to the switching element, each of which is suitable for different scenarios, there is no absolute advantage or disadvantage, the key is "the right medicine for the right disease".


Selection Tips: 
If both 24V DC solenoid valves and 230V AC motors in the system, different types of modules can be mixed and matched, or relay output modules (supporting both AC and DC) can be chosen. 
For inductive loads, is preferred to use transistor or SSR output modules, combined with protection measures such as flyback diodes and RC absorption circuits to avoid voltage spikes that could damage the module. III. Must-see Parameters: In addition to voltage and current, these indicators cannot be ignored
1. Channel Number and Total Current Limit
Channel Number: Choose according to the of loads, with a 10%-20% spare channel reserved (e.g., if controlling 4 devices, choose an 8-channel module), easy expansion in the future. 
Total Current Limit: Some modules meet the current requirement per channel, but the total current will exceed the limit when all channels work simultaneously. For, a module with a single channel of 2A and a total current of 8A will trigger overcurrent protection if all 8 channels drive 2A loads simultaneously.


2. Protection Functions: "Protection is King" in industrial scenarios
The industrial site has complex interference, and comprehensive protection functions can greatly improve the reliability of the system. focus is on 3 points: 
Overcurrent / Short-circuit Protection: When the load is short-circuited or the surge current is too large, the can quickly cut off the output to avoid burning itself and the controller. 
Overvoltage / Surge Protection: Through TVS diodes (Transient Voltage Suppressors to clamp voltage spikes, which is essential for inductive load scenarios. High-quality modules can withstand ±1kV surge pulses and 12kV ESD shocks. Heat Protection: When the module works for a long time or is overloaded, it will automatically reduce the output power or cut off the output to prevent damage from overheating.


3. Response Time and Diagnostic Function
Response Time: For high-frequency switching scenarios (such as high-speed sorting), choose modules with a response time ≤ms; within 10ms is sufficient for ordinary scenarios. 
Fault Diagnosis: High-end modules support channel open circuit, short circuit, and overload diagnosis and feed fault information back to the controller, making it easy to quickly locate the problem. For example, the Beckhoff KL3104 module can transmit fault status through ECAT without the need for on-site inspection one by one.

IV. Practical Selection Case: From Theory to Implementation
Let's look at different selection schemes under needs based on actual scenarios:
Case 1: 24V DC Solenoid Valve (Inductive Load, Switching Frequency 10Hz)
 Parameters: 24V DC, Rated Current 0.8A, Surge Current 3A
Selection Scheme: Transistor Output Module (Switching Frequencyets Requirements), Single Channel Current ≥ 1A, with Overcurrent Protection and Surge Suppression. S7-1200 Series Transistor DO Module fromemens is recommended, or Beckhoff KL3104 (Single Channel 2A, supports EtherCAT communication).
Key Configuration: Diodes in parallel at module output end to absorb the reverse electromotive force.
Case 2: 230V AC Motor (Inductive Load, Switching Frequency 05Hz)
Load Parameters: 230V AC, Rated Current 5A, Surge Current 20A
Selection Scheme: Relay Output ModuleAdapted for Low Frequency Scenarios), Single Channel Current ≥ 8A, Total Current ≥ 5A. Siemens QY10 is recommended (Single Channel 8A, supports 240V AC load).
Key Configuration: Series RC absorption circuit on the motor side to suppress voltage spikes.Case 3: High-Speed Sorting Machine Solenoid Valve (Inductive Load, Switching Frequency 5kHz)
Load Parameters: 24V, Rated Current 0.5A, Surge Current 2A
Selection Scheme: SSR Output Module (Frictionless at High Frequencies), Switchingrequency ≥ 10kHz, with Thermal Protection. Analog Devices MAX14913 is recommended (200kHz switching frequency, built-in surge).


V. Avoiding Pitfalls in Selection: Don't Make These 5 Mistakes!
Driving AC Loads with Transistor Modules: Transistor only support DC loads, and connecting AC loads will immediately burn out the module.
Ignoring Surge Current: Selecting only by rated current can lead to frequent triggering of over protection. For example, using a 0.5A channel to drive a solenoid valve with a surge current of 3A will inevitably fail.
No Protection foructive Loads: Not connecting a flyback diode or RC absorption circuit, the module channel will soon be punctured by the reverse electromotive force.
Shared Mod for Mixed Voltage Loads: 24V DC and 230V AC loads connected to the same module will cause equipment damage due to voltage mismatch.
oring Ambient Temperature: Using ordinary modules in a low-temperature environment of -30°C will lead to switching failure due to component failure.


Summary: Selection Logic Mant
Finally, here's a selection mantra for you to remember to avoid 90% of the pitfalls:
"First determine the load type, then calculate the voltage current;
For high frequency choose transistor / SSR, for low frequency choose relay;
Add protection for inductive loads, don't forget environmental parameters;
Look at the current for the channel, and make sure the protection functions are complete."
There is no "universal" selection for digital output modules, only the "best fit". As as you focus on the load characteristics, combine the switching requirements and environmental conditions, you can choose the module with the highest cost performance and reliability, and fortify the "last mile defense of the automation system.